logobeta
본 영문본은 리걸엔진의 AI 번역 엔진으로 번역되었습니다. 수정이 필요한 부분이 있는 경우 피드백 부탁드립니다.
텍스트 조절
arrow
arrow
(영문) 서울중앙지방법원 2017.08.29 2015가단5382252
구상금
Text

1. The Defendant’s KRW 101,792,135 as well as the Plaintiff’s annual rate of 5% from March 16, 2016 to August 29, 2017.

Reasons

1. Facts of recognition;

A. (1) On July 18, 2013, the Plaintiff entered into an insurance policy with C, which operates the “B Et” (hereinafter “instant Et”) with the insurance period fixed from July 18, 2013 to July 18, 2016. The Defendant is a participant who operates D’s “D” by the repair company specialized in the compliance line.

(2) On October 12, 2014, at around 23:50, a fire (hereinafter “instant fire”) occurred in the Baart liquor warehouse, and the Plaintiff paid 169,653,559 won to the policyholder C with the insurance proceeds from fire damage.

(3) On the other hand, as a result of a sudden increase in temperature in the air conditioners at least three hours prior to the occurrence of the instant fire, “the air conditioners, installed in BE,” the BE requests repair from the Defendant who operates the repair company, and F, an employee of the Defendant, refers to “the reverse air conditioners and devices connected to the said air conditioners,” which are “the air conditioners and devices protecting AE et al.” connected to the said air conditioners.

)가 고장난 상태라 판단한 후 신호단자에 함께 물리도록 연결하여 안전장치를 경유하지 않도록 결선하고, 압축기를 다시 작동시켜 같은 날 20:40경 수리를 마쳤다. 나. 서울지방경찰청의 화재사건 현장감식 결과 (1) 이 사건 냉장고 압축기 1, 2, 3(우측부터 #1, #2, #3로 구분함, 보고서는 좌측에서 우측으로 순서를 정함에 따라 #1 압축기가 됨 의 모터 안전장치는 각 압축기 내부에 인가되는 전원의 역상 및 내부의 온도를 감지하는 센서로서 안전장치로부터 컨트롤함의 신호단자에서 수신하여 전자접촉이의 개폐 신호로 사용하도록 설치되어 있으나 신호단자에서 2개선을 양층 단자에 함께 연결함으로써 사실상 모터 안전장치가 제거된 상태로 결선되어 있고, 컨트롤함으로 인가되는 전원의 역상을 감지하는 장치의 신호선이 1개의 단자에...

arrow